PROFIdrive parameters
101
PROFIdrive parameters
Table 22. PROFIdrive profile-specific parameters.
Para-
meter
R/W
*
Data type Description
915 R/W Array [10] Unsigned16 Assignment PZD1 to PZD10 in PPO-write
916 R/W Array [10] Unsigned16 Assignment PZD1 to PZD10 in PPO-read
918 R/W Unsigned16 Node address. Writing this parameter will
change the node address if the rotary
switches have the setting 0. Module re-
start required.
919 R Octet String4 Device system number.
927 R/W Unsigned16 Operator control rights (parameter
identification, PKW).
Value Mode
0 Parameters cannot be
written, only read (927 can
be written)
1 Parameters can be written
and read (default).
928 R/W Unsigned16 Control rights (process data, PZD).
Value Mode
0 PZD part is disabled, i.e.
Receipt of new PZD data is
ignored
1 PZD part is enabled
(default).
929 R Unsigned16 Selected PPO-type
Value PPO-type Configuration
1 PPO1 F3h, F1h
2 PPO2 F3h, F5h
3 PPO3 F1h
4 PPO4 F5h
5 PPO5 F3h, F9h