PROFIdrive parameters
102
930 R/W Unsigned16 Selection switch for operation mode.
Value Mode
1 Speed control mode: Control
word and status word for
frequency/speed used.
8001h Speed control mode: Control
word and status word for
torque used.
933 R/W Unsigned16 Selection switch for Control word, bit 11.
Value Module Control word bit
0 None
1 to 5 Vendor specific 1 to 5*
* The meaning of vendor specific bits is
defined by drive application program.
934 R/W Unsigned16 Selection switch for Control word, bit 12.
(See parameter 933 for coding)
935 R/W Unsigned16 Selection switch for Control word, bit 13.
(See parameter 933 for coding)
936 R/W Unsigned16 Selection switch for Control word, bit 14.
(See parameter 933 for coding)
937 R/W Unsigned16 Selection switch for Control word, bit 15.
(See parameter 933 for coding)
939 R/W Unsigned16 Selection switch for Status word, bit 11.
Value Module Status word bit
0 None
1 to 3 Vendor specific 1 to 3*
* The meaning of vendor specific bits is
defined by drive application program.
940 R/W Unsigned16 Selection switch for Status word, bit 12.
(See parameter 939 for coding)
941 R/W Unsigned16 Selection switch for Status word, bit 13.
(See parameter 939 for coding)
942 R/W Unsigned16 Selection switch for Status word, bit 14.
(See parameter 939 for coding)
Para-
meter
R/W
*