Fault tracing
99
Fault tracing
LED indications
The RPBA-01 module is equipped with three diagnostic LEDs.
The description of the LEDs is below.
Name Colour Function
ERROR
Red
Flashing 1 Hz - Error in configuration:
Internal configuration mismatch.
Flashing 2 Hz - Error in User Parameter data:
The length/contents of the User Parameter data
set during initialisation of the module is not equal
to the length/contents set during configuration of
the network. Check that the selected DP mode
matches the GSD file used (see configuration
parameter 21 DP MODE on page 37).
Flashing 4 Hz - Error in initialisation of the
PROFIBUS communication ASIC.
Off - No diagnostics present
On-Line
Green
Lit - Module is On-Line and data exchange is
possible.
Off - Module is not On-Line
Off-Line
Red
Lit - Module is Off-Line and no data exchange is
possible.
Off - Module is not Off-Line