DP-V1 communication
86
16h Parameter address
impermissible
Illegal value or value that is not
supported for the attribute, number of
elements, parameter number or sub-
index, or a combination
17h Illegal format Write request: Illegal format or format of
parameter data that is not supported
18h Number of values inconsistent Write request: Number of values of
parameter data does not match number
of elements at the parameter address
65h
FF
Manufacturer-specific
65h Vendor-specific error Vendor-specific error
66h Request not supported Request not supported
67h Communication error Request cannot be completed because
of communication error
68h …
6Dh
Manufacturer-specific
6Eh Non-volatile error Failure during write to non-volatile
memory
6Fh Time-out error Request aborted because of timeout
70h …
77h
Manufacturer-specific
78h PZD map failure Parameter cannot be mapped to PZD
(size mismatch or non-existent)
79h PZD memory failure Parameter cannot be mapped to PZD
(out of memory)
7Ah Multiple PZD map Parameter cannot be mapped to PZD
(multiple PZD write)
7Bh …
81h
Manufacturer-specific
82h Control word bit map Cannot map Control word bit
(parameter 933…937, e.g. double
mapping of bits)