Ekip Dip | 8 - Additional functions47 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D
8 - Additional functions
Additional functions
Ekip T&P, Ekip Programming and Ekip Bluetooth allow the Trip unit to be connected to Ekip Connect software
and to access parameters and commands that are not directly available from the front interface; the main
ones are:
Name Description
Maintenance
Function allowing the user to be informed that more than a year has passed
since the last maintenance or that contact wear has increased by more than
10%
Local Bus
Bus activation so as to communicate with Ekip Link, Ekip Multimeter or Ekip
Signalling 10K modules
Programmable states
Programmable states for monitoring events, to associate with the Ekip
Signalling 10K contacts
Programmable Functions
Commands which activate according to the state of signals or events
programmable by the user
Led Alive Configuration of the Power led of the Trip unit and of all modules connected
Details of these and other parameters are given in manual 1SDH001330R1002.
9 - Default parameters
Ekip Dip default parameters
The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front DIPs
(protections, Frequency, Neutral), other via front bus.
Protection/Parameter Value
L 1 In; 144 s
S
(1)
Off; 0.1 s
I 4 In
G
(1)
Off; 0.1 s
Frequency 50 Hz (IEC) / 60 Hz (UL)
Neutral
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Hardware Trip Disabled
Local Bus Off
Alive LED Disabled (Power-on LED fixed)
Maintenance Off
(1)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.