82 | © 2020 ABB | 1SDH001821A1002 - ECN000135670 Protections | 15 - Additional protections and functions
RC Protection
Rc
Idn
t
I
tdn
Function
Rc protection protects against the residual current earth faults by detecting the fault current with the
appropriate external Rc toroid.
The protection sends a TRIP command if the current from toroid Rc exceeds threshold Idn for longer than
Tdn.
To check and simulate the trip times in relation to all the parameters, please consult:
summary table of the protections with the operating characteristics (page 87)
the graph with trip curve (page 97)
Parameters
Parameter Description Default
Threshold Idn
Defines the value that activates the protection; the value is given in
Amperes and can be set within a range of values from 3 A to 30 A
5 A
Time Tdn
This is the trip time of the protection; the value is given in seconds and
can be set within a range of values from 0.05 s to 0.8 s
0,06 s
Limitations and additional functions
Ekip Touch activates and displays the Rc protection parameters if the following conditions are observed:
Rating Plug Rc model assembled and installed
Measurement module assembled and installed
protection activation includes checking for the presence of toroid Rc and signaling on the diagnosis bar in
the event of alarm/absence