ABB | SACE Tmax XT
90 | © 2020 ABB | 1SDH001821A1002 - ECN000135670 Protections | 17 - Performance table
Note on protections
(1)
use trip and threshold current values expressed in In for calculating t
t
(example: If = 0.8 In, I1= 0.6 In)
(2)
with t4 = instantaneous, the maximum tolerance is 50 ms
(3)
Tolerance values valid with Trip unit at steady state or on with auxiliary power supply, trip time 100 ms,
temperature and signals within operating limits; the tolerances in the table after the notes are applicable if the
conditions are not guaranteed
(4)
the trip unit considers a 3% hysteresis for clearing from the alarm condition
(5)
tolerance valid for frequencies within range: fn ± 2 %. A ± 5% tolerance is applicable for off range
frequencies
(6)
± 20% for threshold 0.4 Hz / s
(7)
time to be considered valid after Motor start-up
(8)
time to be considered valid with protection in alarm status after Motor start-up; if the alarm appears during
Motor start-up, the trip unit calculates and uses the lowest value between tu and the half of Motor start-up
(9)
maximum trip time
(10)
with If 18 kA, t
t
3 ms;
with If < 18 kA and If I31 * 3, t
t
7 ms (If three-phase) or t
t
9 ms (If single-phase);
with If < 18 kA and If < I31 * 3, t
t
15 ms.
(operating parameters guaranteed with Vaux auxiliary power supply)
(11)
tolerance valid with threshold U14 > 10%; with U14 10% (and >6%), the tolerance is 10%; with U14 <
5%, the tolerance is 15%
Performance guaranteed in all operating conditions
Protection Trip threshold tolerance Trip time tolerance
L Activation within range: (1.05 to 1.2) x I1 ± 20 %
S ± 10 % ± 20 %
I / 2I ± 15 % 60 ms
G ± 15 % ± 20 % (60 ms with t4 = instantaneous)
Gext ± 15 % ± 20 %
MDGF ± 15 % ± 20 %
UF / UF2 /
OF / OF2
± 2 % ± 20 %
RV ± 10 %
± 20 %; in the case of single-phase self-supply:
the highest between ± 20 % and 30 ms
Other -- ± 20 %