IEC18000675 V1 EN-US
Figure 44: PCM600: Common Write
Common Write collects information from the hardware modules, configured ports, parameters
along with already configured sampled values and write the configuration to a SAM600
system. The process is shown in the below flow chart, see
Figure 45.
The following attribute values are validated when the Common Write action is initiated from
PCM600:
Technical Key
Number of SAM600 modules
Type of SAM600 modules
Serial Number
Order of SAM600 modules
Interconnection between SAM600 modules
The above mentioned attribute values are confirmed for the Common Write to start. If there
are any discrepancies during the above validations, along with the additional confirmation
from the user, Common Write is aborted and the appropriate error message is displayed on
the PCM600 output window.
Section 6 1MRK 511 433-UEN B
Communication with PCM600 and SAM600 system
42 SAM600 Process Bus I/O System
Engineering manual