Section 10 SAM600 parameter settings
GUID-F87199EF-D9A2-41B9-B403-DF6F69A4E705 v1
The following tables list the SAM600 parameter settings. Parameters can be set for each
SAM600 module individually or globally for the whole SAM600 system. In some instances
global settings can be overwritten by module-individual settings.
Parameter Power system frequency Unit
Description The frequency of the power
system of a connected SAM600
module.
Module Type All
Level SAM600 System
Value Range 50 or 60 Hz
Default 50 Hz
Parameter Primary nominal transducer value Unit
Description Rated voltage or current on the
primary side of the measurement
transformer. For the SAM600-VT it
is defined as the line-line value.
Module Type SAM600-CT and SAM600-VT
Level SAM600 Module
Value Range SAM600-CT: 1..65000
SAM600-VT: 1..1100
A
kV
Default SAM600-CT:1000
SAM600-VT: 110
A
kV
Parameter Secondary nominal transducer
value
Unit
Description Rated voltage or current on the
secondary side of the
measurement transformer.
For the SAM600-VT it is defined as
the line-line value.
Module Type SAM600-CT and SAM600-VT
Level SAM600 Module
Value Range SAM600-CT-1 (constant)
SAM600-CT-5 (constant)
SAM600-VT: {100, 110, 115, 120,
125}
A
A
V
Default SAM600-VT: 110 V
1MRK 511 433-UEN B Section 10
SAM600 parameter settings
SAM600 Process Bus I/O System 55
Engineering manual