Parameter SmpSynch backwards compatibility
Description Defines the behavior if the Time synchronization mode Free running is
configured. In this case, the SmpSync shall be indicated as True or False.
Module Type All
Level SAM600 System
Value Range True, False
Default False
Parameter Open IRF contact on System Bus single redundancy error
Description Open IRF contact on a System Bus single redundancy error.
Module Type All
Level SAM600 System
Value Range True, False
Default False
Parameter Time synchronization mode
Description The parameter defines the synchronization mode for a SAM600 system.
Module Type All
Level SAM600 System
Value Range Free running, Pulse per second, Grandmaster clock with GPS, Master clock
Default Free running
Parameter IEEE1588 Domain Number
Description The parameter defines the PTP domain in which SAM600 system operates.
Module Type All
Level SAM600 System
Value Range 0-255
Default 0
Parameter SAM600 System Technical Key
Description Identifier of a SAM600 system.
Module Type All
Level SAM600 System
Value Range String[64]
Default AA0B0Q0KF0
Parameter Customer-provided name to identify the individual SAM600 module
Description Designator of a module.
Module Type All
Level SAM600 Module
Value Range String[48]
Default empty string
1MRK 511 433-UEN B Section 10
SAM600 parameter settings
SAM600 Process Bus I/O System 57