29
The parameters stored in the EEPROM have
been given default values after factory testing.
All the default values have been stored in the
EEPROM by pressing the push-buttons STEP
and SELECT at the same time as the auxiliary
power supply was connected. The push-but-
tons have to be pressed until the display is lit.
The following table gives the default values of
the parameters.
Default values of
the parameters
Parameter Channel Code Default value
Open pulse lenght 2 V5 0.1 s
Close pulse lenght 2 V6 0.1 s
kWh value per pulse 0 S3 1 kWh per pulse
Object indication mode 0 S7 0 = continuous display
Display indication mode 0 S8 0 = continuous display
Scaling of current measurement 0 S9 200.00
Low limit of mA-signal of active power 0 S12 +4 mA
High limit of mA-signal of active power 0 S13 +20 mA
Low limit of mA-signal of react. power 0 S14 +4 mA
High limit of mA-signal of react. power 0 S15 +20 mA
Active power corresponding to the
mA-signal at low limit 0 S16 +0.00
Active power corresponding to the
mA-signal at high limit 0 S17 +999.99
Reactive power corresponding to
the mA-signal at low limit 0 S18 +0.00
Reactive power corresponding to
the mA-signal at low limit 0 S19 +999.99
Power measurement 0 S91 0 = no power measurement
Energy measurement 0 S92 0 = no energy measurement
Configuration and interlocking 0 S100 1 = default configuration and
interlocking 1
Configuration of objects 0 S101 default configuration 1,
: see appendix 1
S116
Program/run mode selection 0 S198 1 = run mode
Interlocking selection 0 S199 1 = interlockings in use
Interlocking program 0 M200 default interlocking 1,
: see appendix 1
M300
Event delay; —>10 (open) 1…3 S10 0.0 s
Event delay; —>01 (close) 1…3 S11 0.0 s
Event delay; —>00, —>11 1 and 3 S12 10.0 s
Event delay; —>00, —>11 2 S12 0.2 s
Use of input 7 7 S1 0 = general mode
Operation direction of intputs 4…13 4…13 S2 1 = active at high state
Signal output activation by
inputs 4…13 4…13 S3 0 = no signal output
Operation of OPEN and CLOSE
outputs by inputs 4…13 4…13 S4 0 = no activation or inhibit
Memory controlled function of the 4…9 S5 0 = not memory controlled
indicators of the binary inputs