6 TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A
2 Use in potentially explosive
atmospheres according to ATEX
and IECEx
NOTICE
— Further information on the approval of devices for use
in potentially explosive atmospheres can be found in
the explosion protection test certificates (at
www.abb.com/temperature).
— Depending on the design, a specific marking in
accordance with ATEX or IECEx applies.
2.1 Ex-marking
2.1.1 Transmitter
ATEX intrinsic safety
The device fulfills the requirements of Directive 2014/34/EU
in case of corresponding purchase orders and is approved
for use in Zone 0, 1 and 2.
Model TTF200-E1
Type Examination Test
Certificate:
PTB 05 ATEX 2017 X
II 1 G Ex ia IIC T6 Ga
II 2 (1) G Ex [ia] ib IIC T6 Gb (Ga)
II 2 G (1D) Ex [iaD] ib IIC T6 Gb (Da)
ATEX flameproof enclosure
Approved for use in Zone 1 and 2.
Model TTF200-E3
Type Examination Test
Certificate:
PTB 99 ATEX 1144
II 2G Ex d IIC T6 Gb
ATEX flameproof enclosure and intrinsic safety
Approved for use in Zone 1 and 2, in case of intrinsic safety
also for use in Zone 0.
Model TTF200-E4
Type Examination Test
Certificate:
PTB 99 ATEX 1144
PTB 05 ATEX 2017 X
II 2G Ex d IIC T6 Gb
II 1G Ex ia IIC T6 Ga
IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
Model TTF200-H1
IECEx Certificate of Conformity IECEx PTB 09.0014X
Ex ia IIC T6...T1 Ga
Ex [ia] ib IIC T6...T1 Gb (Ga)
Ex [ia IIIC Da] ib IIC T6...T1 Gb
IECEx flameproof enclosure
Approved for use in Zone 1 and 2.
Model TTF200-H5
IECEx certificate of conformity IECEx PTB 12.0039
Ex d IIC T1-T6 Gb
2.1.2 LCD indicators
ATEX intrinsic safety
The device fulfills the requirements of Directive 2014/34/EU
in case of corresponding purchase orders and is approved
for use in Zone 0, 1 and 2.
Type Examination Test
Certificate
PTB 05 ATEX 2079 X
II 1G Ex ia IIC T6 Ga
IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
IECEx certificate of conformity IECEx PTB 12.0028X
Ex ia IIC T6