28 TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B
… 8 Commissioning
… Parameterization of the device
DTM menu path, parameters Description
<Device> / <Configuration>
<Sensor / Reference junction> Internal: use of the internal reference junction of the transmitter when using a thermocouple / compensating cable
(relevant for all thermocouples except for type B)
External - fixed: transfer of thermal cable / compensating cable via copper material at constant thermostat
temperature
Without: no reference junction
<Sensor / Reference junction
temperature>
Relevant for external reference junction, specification of constant external reference junction temperature
Value range: 50 to 100 °C
<Device > / <Parameterize>
<Measuring range of PV / unit> Selects the physical unit for the sensor measuring signal
Units: °C, °F, °R, K, mV, Ω, mA
<Measuring range of PV / lower range
value>
Defines the value for 4 mA (adjustable)
<Measuring range of PV / upper range
value>
Defines the value for 20 mA (adjustable)
<Current output / damping> Configurable τ 63% output signal damping value
Value range: 0 to 100 s
<Current output / output upon error >
(overrange)
Generates a high alarm signal in the event of a sensor or device error; can be configured 20 to 23.6 mA
Standard 22 mA
<Current output / output upon error >
(underrange)
Generates a low alarm signal in the event of a sensor or device error; can be configured 3.5 to 4 mA
<Device> / <Maintenance>
<Poll address / TAG> (HART TAG) Defines the HART TAG name.
8 characters, alphanumeric
<Poll address / TAG>
(Address (Multidrop))
Specifies the communication type
Address = 0 conforms to HART operating mode: point-to-point communication, 4 to 20 mA output signal
Address = 1 to 15 conforms to HART multidrop operating mode output signal 3.6 mA, only the digital HART measured
values are available
<Adjustment> (Set lower range value) Temperature correction for specified / simulated sensor lower range value to target lower range temperature value
Set Trim low or lower range value > OK
<Adjustment /DAC adjustment fixed
for zero at 4 mA>
Output signal correction for specified / simulated sensor LRV value to 4.000 mA set point
Analog current measurement value input 3.5 to 4.5 mA
<Adjustment /DAC adjustment fixed
for amplification at 20 mA>
Output signal correction for specified / simulated sensor URV value to 20.000 mA set point
Analog current measurement value input 19.5 to 20.5 mA
<Device> <Simulation> Output signal simulation corresponding to the value specified
Value range: 3.5 to 23.6 mA