EasyManua.ls Logo

ABB TTF200 - 2 Use in Potentially Explosive Atmospheres; ATEX and IECEx Marking and Approvals

ABB TTF200
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 5
2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx
Change from one to tw o columns
Note
Further information on the approval of devices for use in
potentially explosive atmospheres can be found in the
explosion protection test certificates (at
www.abb.com/temperature).
Depending on the design, a specific marking in accordance
with ATEX or IECEx applies.
In devices with combined types of protection, for example
TTF200-E4, observe the ‘Product Identification’ chapter in
the operating or commissioning instruction before
commissioning.
Ex marking
Transmitter
ATEX intrinsic safety
The device fulfills the requirements of Directive 2014/34/EU in
case of corresponding purchase orders and is approved for use
in Zone 0, 1 and 2.
Model TTF200-E1
Type Examination Test Certificate PTB 05 ATEX 2017 X
II 1 G Ex ia IIC T6 Ga
II 2 (1) G Ex [ia IIC Ga] ib IIC T6 Gb
II 2 G (1D) Ex [ia IIIC Da] ib IIC T6 Gb
ATEX flameproof (enclosure)
Approved for use in Zone 1 and 2.
Model TTF200-E3
Type Examination Test Certificate PTB 99 ATEX 1144 X
II 2G Ex db IIC T6/T4 Gb
ATEX flameproof (enclosure) and intrinsic safety
Approved for use in Zone 1 and 2, in case of intrinsic safety also
for use in Zone 0.
The ‘E4’ coding combines the following types of protection:
‘Intrinsic safety’, (TTF200-E1) and ‘Flameproof (enclosure)’,
(TTF200-E3). Devices with combined types of protection may
only be operated in one of the possible types of protection.
For this purpose, observe the ‘Product Identification’ chapter in
the operating or commissioning instruction before
commissioning.
Model TTF200-E4
Type Examination Test Certificate PTB 99 ATEX 1144 X
PTB 05 ATEX 2017 X
II 2G Ex db IIC T6/T4 Gb
II 1G Ex ia IIC T6 Ga
IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
Model TTF200-H1
IECEx certificate of conformity IECEx PTB 09.0014X
Ex ia IIC T6...T1 Ga
Ex [ia IIC Ga] ib IIC T6...T1 Gb
Ex [ia IIIC Da] ib IIC T6...T1 Gb
IECEx flameproof (enclosure)
Approved for use in Zone 1 and 2.
Model TTF200-H5
IECEx certificate of conformity IECEx PTB 12.0039 X
Ex db IIC T6/T4 Gb
LCD indicator
ATEX intrinsic safety
The device fulfills the requirements of Directive 2014/34/EU in
case of corresponding purchase orders and is approved for use
in Zone 0, 1 and 2.
Type Examination Test Certificate PTB 05 ATEX 2079 X
II 1G Ex ia IIC T6 Ga
IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
IECEx certificate of conformity IECEx PTB 12.0028X
Ex ia IIC T6

Table of Contents

Other manuals for ABB TTF200