Mounting
12 - EN TTF300 CI/TTF300-EN
3.1 Position of LCD indicator
A00269
2
1
Fig. 4
1 Front view 2 Rear view of LCD indicator / plug
positions
Warning - General dangers!
If the transmitter is located in an explosive atmosphere, there is a risk of explosion.
Make sure there is sufficient fresh-air ventilation.
The position of the LCD indictor can be adjusted to suit the installation position of the
transmitter, to ensure that the display is as clearly legible as possible. There are 4 positions at
increments of 90°.
To adjust the position, proceed as follows:
1. Tighten the lock screw under the housing cover.
2. Release the housing cover by turning it counterclockwise.
3. Carefully pull the LCD indicator to release it from its holder.
4. Carefully insert the LCD indicator in the required position.
5. Screw the housing cover back on.
6. Loosen the lock screw until the housing cover is firmly in place.