39
1
Fig. 4.1 From System Overview screen you will find
Switch status and Supply info views, and by pressing Up
and Down -keys (2), you can go forward to see Voltages
and Synchronization view, see the table below.
System Overview
S1 Ok Not Ok S2
11:06
S1 Connected to Load
G
Voltages (S1)
U1 - - -
U2 - - -
U3 - - -
U0 - - -
11:06
U12 - - -
U23 - - -
U31 - - -
G
4. Navigating HMI menu
4.1 Start Screens
Start screens
System Overview (Switch status)
Shows voltages and frequencies of both supplies
and the switch position.
Supply info view
Shows Phase to Phase voltages of both supplies
and the frequencies.
Voltages (S1)
S1 phase voltages
S1 line voltage
Voltages (S2)
S2 phase voltages
S2 line voltage
Synchronization view
Enabled only when In-phase monitor is on.
Show the time to next sync, sync period
Current view
Enabled only when current measurement module is
connected.
Phase currents
Neutral current
Residual current
Active Power view
Enabled only when current measurement module is
connected.
Active power by phase
Total active power
Reactive Power view
Enabled only when current measurement module is
connected.
Reactive power by phase
Total reactive power
Apparent Power view
Enabled only when current measurement module is
connected.
Apparent power by phase
Total apparent power
Energy Counters view
Enabled only when current measurement module is
connected.
Active energy by source
Reactive energy by source
Apparent energy by phase
Total active energy
Total reactive energy
Total apparent energy