Manual ZX0 HB 600 en - Revision 05 | 15
Fig. 2.1.3.2: Greasing the light, outer area of the blanking plug for the bus-
bar bushing in the area between the arrows
Cleaning the sockets, the contact tubes and the outer
cone
Degrease and clean the mating piece for the silicone
insulating part (the busbar socket or socket for the voltage
transformer) with intensive cleaner M.X.T. 60 forte.
Clean the outer cone on the cable connector with intensive
cleaner M.X.T. 60 forte.
?
Assemble the components immediately to avoid
soiling.
Fig. 2.1.3.4: Greasing the silicone insulating part of the blanking plug for
voltage transformer sockets in the area between the arrows
Fig. 2.1.3.1: Greasing the light, outer areas of the silicone insulating part on
the busbar connection
Fig. 2.1.3.3: Greasing the silicone insulating part of the voltage transformer
in the area between the arrows