EasyManua.ls Logo

ABB ZX0 - Test Procedures; Testing for the off-circuit condition

ABB ZX0
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
64 | Manual ZX0 HB 600 en - Revision 05
The off-circuit condition on the cable side is tested by means of
the capacitive voltage indicator (pick-off on the outer cone). Three
systems can be used:
− LRM-system,
KVDS-system, or
− CAVIN-system.
Observe the instruction manual for the system used.
− Check the function of the equipment immediately before
use. The optical display must be clearly visible!
The sockets of the capacitive indicator system must never
be short-circuited, except during voltage testing on the
switchgear.
Testing for the off-circuit condition is performed with the display on
the unit. No separate display unit is required.
5 Test procedures
5.1 Testing for the
off-circuit condition
Fig. 5.1.1.1: LRM system with display unit
Testing for the off-circuit condition is performed with a plug-in dis-
play unit (design to IEC 61243-5) at the three pairs of measuring
sockets.
Perform repeat tests on the system in accordance
with IEC 61243-5, for instance with interface tester
KSP. Observe the instructions for the interface
tester.
5.1.1 LRM-system
5.1.2 KVDS- and CAVIN-systems
Fig. 5.1.2.2: CAVIN-system
Fig. 5.1.2.1: KVDS-system

Table of Contents

Related product manuals