51
3.4.1 Normal Mode Start-up
(1) On the rear of UPS, switch ON the AC Power switch.
(2) Close UPS Mains Input Breaker/Switch and Bypass Input Breaker if equipped.
(3) Select CommandOperationNormal Mode on LCD display.
(4) Return to the Mimic Display. Wait for few minutes, the rectifier will have started.
(5) Close the battery switch/fuses to connect the batteries after rectifier has been turned on.