(6) The inverter will have started and supply output voltage.
(7) Close the UPS Output Breaker to supply the power to the load.
3.4.2 Cold Start
(1) User can start-up the UPS using the battery when main input power is not available.
(2) If the UPS is with an external battery configuration, it is imperative that the batteries are
connected.
(3) On the rear of UPS, push button and hold down the button that indicates Batt. Startfor a
minimum of 10 seconds.
(4) Select CommandOperationColdStart Precharge Ready on LCD display.
(5) Select Normal Mode to start UPS.
(6) Once UPS working in Normal Mode.
3.4.3 Shutdown
(1) Select CommandOperationShutdown on LCD display.
Attention:
IMMEDIATE LOAD OFF!
For turn off the working power, switch OFF both AC Power and Batt. Power switches in
the rear of UPS.