52
(AC Mode )
<105% continuous
>106%~120% for 30 seconds transfer to bypass
>121%~150% for 10 seconds transfer to bypass
>150% for immediately transfer to bypass
Buzzer continuously alarms.
(Battery Mode)
<105% continuous
>106%~120% for 30 seconds shuts down
>121%~150% for 10 seconds shuts down
>150% for immediately shuts down
Buzzer continuously alarms.
Overload
(Bypass Mode)
<105% continuous
>106%~120% for 250 seconds shuts down
>121%~130% for 125 seconds shuts down
>131%~135% for 50 seconds shuts down
>136%~145% for 20 seconds shuts down
>146%~148% for 5 seconds shuts down
>149%~157% for 2 seconds shuts down
>158%~176% for 1 seconds shuts down
>177%~187% for 0.32 seconds shuts down
>188% for 0.16 seconds shuts down
Buzzer continuously alarms.
Short Circuit
Bypass mode : Input Fuse/Input Breaker
Normal Mode: Output Breaker/Electronic Circuit
Battery Mode: Output Breaker/Electronic Circuit
Battery ABDM
EPO UPS shuts down immediately
Normal Mode Transfer to Bypass Mode
Over
Temperature
Battery Mode UPS shuts down immediately
Audible Alarm
Battery Mode Sounding once every 1.5 seconds
Low Battery Sounding once every 0.2 seconds
Overload Sounding once every 3 second
Fault Continuously Sounding(or Sounding once every 3 second)
53
Physical
Dimensions(HxWxD in mm)
88(2U)x440x
405
88(2U)x440x
405
88(2U)x440x 650
88(2U)x440x
650
115V 34.5Ib(15.7kg) 34.5Ib(15.7kg) 61.3lb(27.9kg) 68.6Ib(31.2kg)
Weights
230V 34.2Ib(15.1kg) (not available) 62.0lb(28.2kg) 65.5Ib(29.8kg)
115V NEMA 5-15P NEMA 5-15P NEMA 5-20P NEMA L5-30P
Input Connection
230V
10A, IEC 320-
C14
(not available)
10A, IEC
320-C14
16A, IEC
320-C20
115V 5-15R×6 5-15R×6
5-15R×2
5-20R×2
5-15R×4
L5-30R×1
Output Connection
230V
(6) 10A,IEC
320-C13
(not available)
(6) 10A,IEC 320-
C13
(4) 10A,IEC
320-C13
(1) 16A,IEC
320-C19
Environmental
Operation Temperature 0-40℃
Noise Level <50dBA
Relative Humidity 0 to 90% (Without condensation)
Interface
Interface Type 1 *USB port+ 1*RS-232 port
SNMP(option) Power management from SNMP manager and Web browser
Compatible platforms Windows 95/98/NT/2000/XP Novell NetWare, Linux, etc.
Standards and Certification
Safety IEC/EN 62040-1-1,IEC 60950-1
Performance IEC/EN 62040-3
EMC
IEC/EN62040-2 Class A, FCC Part 15 Subpart B Class A,
IEC/EN55011, CISPR11, IEC61000-4-2/-3/-4/-5, IEC61000-2-2,
IEC61000-3-2/-3
Markings CE,UL, cUL, FCC