EasyManua.ls Logo

Ablerex TAURUS 20 kVA - MIMIC Display

Default Icon
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.3 Mimic Display
Ais Rectifier、【Bis Static Switch and Cis Inverter.
Thefade pattern indicatesthispart isn’t activated.
The blue pattern indicates this part is activated.
The red pattern indicates this part is occurred abnormal condition.
DDisplay the bypass input measurements.
EDisplay the mains input measurements.
FDisplay the output measurements.
The abnormal measurements will have redbackground .
ClickD E F
to change the measure parameter and press for 3
seconds to enter to Real Time Information .
GDisplay the status of battery.
Press it for 3 second to enter to Real Time Information .
The battery isn’t connected.
The green pattern indicates the battery is charging.
The yellow pattern indicates the battery is discharging.
HAlarm silence button. Click it to silence the alarm and press for 3 seconds to
enable/disable the buzzer.
Buzzer is enabled and Buzzer is disabled.
I
Display UPS internal temperature.
Press for 3 seconds to enter to Real Time Information .
JOverload counter
53
192321262008007

Related product manuals