2. Installation and Wiring
2.1 Storage and Installation Environment
Storage Environment
Temperature-20~70
Relative Humidity95%
Installation Environment
A proper installation environment not only ensures the effective operation of the UPS
but also reduces the chance of failure and extends service life. Please take the
following recommendations into account to select the most suitable environment and
reduce the likelihood of accidents.
Temperature0~40 (20~25is recommended for extend batteries life time).
Relative Humidity 95% (without condensation)
Altitude1000m at normal power.Over 1000m above sea level, the maximum output
current must be derated by 1% every additional 100m.
This product must not be used in an environment with sparks, smoke or gas to
prevent arcing, injuryand fire hazards.
Avoid using dusty materials, volatile gases, or corrosive substances with a high salt-
content in the environment where the UPS is installed.
The installation location of the UPS should be well-ventilated. During charging, the
chemical reaction of the battery generates small amounts of gases. If there is a crack
in the battery then this may pose an environmental hazard.
Do not place in a location near a heat source as this will shorten the battery life.
Do not place outdoors and avoid direct exposure to sunlight.
Please ensure that the environment where the UPS is placed is free from animals that
may damage the wiring, such as: rats and other small animals.
Please ensure that the floor is strong enough to hold the UPS and battery. It must
keep the equipment stable to ensure that it won't suffer damage in a fall.
We recommend placing a fire extinguisher near the UPS in case of an emergency.