3.4 Operation Processes
3.4.1 Normal Mode Start-up
Warning!
Please don’t close the battery line switch/fuses before start-up the
rectifier of UPS if the UPS don’t install optional DC Cold Start Kit.
(1) Close UPS Mains Input and Bypass Input Switches.
(2) Select CommandOperationNormal mode on LCD display.
(3) Return to Mimic Display. Wait for few minutes, the rectifier will be started.
44