Recommended Circuit Breaker Size
Input/Output
Voltage
Output Power Mains Input
(1)
Output/Bypass Input
(1)
380 V
10kVA/10kW
30 A
25 A
20kVA/20kW
65 A
50 A
30kVA/30kW
95 A
80 A
40kVA/40kW
125 A
105 A
60kVA/60kW
185 A
160 A
80kVA/80kW
250 A
210 A
400 V
10kVA/10kW
30 A
25 A
20kVA/20kW
60 A
50 A
30kVA/30kW
90 A
75 A
40kVA/40kW
120 A
100 A
60kVA/60kW
175 A
150 A
80kVA/80kW
240 A
200 A
415 V
10kVA/10kW
30 A
25 A
20kVA/20kW
55 A
50 A
30kVA/30kW
85 A
70 A
40kVA/40kW
115 A
95 A
60kVA/60kW
170 A
145 A
80kVA/80kW
230 A
190 A
(1)
The sizing takes into account 150% overload capacity.