PROGRAMMING
VPD MODE (HIGH VPD TRIGGER)
Pressing the up or down button sets the high VPD
trigger. The devices will activate if the probe’s reading
meets or exceeds this threshold.
Once triggered, the devices will gradually ramp up to
the level set in ON mode. If the probe’s reading falls
below this trigger point, the devices will gradually slow
down to a stop or at the level set in OFF mode.
You may set this trigger below the low VPD trigger to create a specific range in which the devices
are active.
Either of the two trigger points can activate while you are in VPD Mode, even if you are viewing another trigger point.
Set a trigger point to OFF if not in use, by holding down the up and down button. If there is a level set in OFF Mode
other than zero the devices will run at that level when triggered to turn o.
ONOFF
TRIGGER POINT
HIGH VPD
HIGH VPDLOW VPD
0
kPa
9.9
kPa
1.1kPa

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AC Infinity CONTROLLER 69 PRO and is the answer not in the manual?

AC Infinity CONTROLLER 69 PRO Specifications

General IconGeneral
ConnectivityWi-Fi, Bluetooth
Power SupplyAC Adapter
CompatibilityAC Infinity Devices
Operating Voltage5V DC
Amperage2A
Sensor Ports4
Fan Ports4
Control Ports4
Weight0.5 lbs
DisplayLCD
ControlManual Control
App CompatibilityiOS and Android

Related product manuals