EasyManuals Logo

Accutron FlowTrax IS User Manual

Accutron FlowTrax IS
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
14 | Page
[1L] Enter moving
average (0 - 255) :
0
In most cases the measured airflow is slightly
turbulent, by averaging the readings, the
analog output will behave in a smoother rate
of change allowing for a better representation
of airflow in the measured area.
Advanced Menu
[2A] Enter calibration
correction:
1.0
The calibration correction allows for a
correction factor to be entered in the case of
difficult applications. It is calculated by
dividing the expected reading / actual reading.
[2B] Enter noise filter
level:
0
value (0-100)
The noise filter is a provision for dealing with
extreme noise. Normally it is set to 0.
[2C] Enter wave detection low
threshold:
20
value (0-100)
This option is used to specify the lower wave
detection threshold in order to properly detect
the ultrasonic signal. In almost all cases this
value should be left at 20.
[2D] Enter wave detection high
threshold:
70
value (0-100)
This option is used to specify the upper wave
detection threshold in order to properly detect
the ultrasonic signal. In most cases this value
should be left at 70.
[2E] Enter dynamic range limiting
factor:
10
value (0-1000)
Places a limit on how much weak signal noise
may be expanded (digitally amplified). It
prevents over amplification of noise in the
absence of a valid signal
.
[2F] Enter detection hysteresis
length:
10
value (0-1000)
This option determines the minimum
acceptable length of the waveform. Default is
50 units.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Accutron FlowTrax IS and is the answer not in the manual?

Accutron FlowTrax IS Specifications

General IconGeneral
BrandAccutron
ModelFlowTrax IS
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals