Section 4: Modbus
The RS485 interface in the Accutron IS is optically isolated from the rest of the unit. This is why an
external source of 5VDC is required.
Note: Do not poll faster than every 500ms.
The default Modbus RS485 settings are:
Modbus Address: 1 (3A)
Baud Rate: 19200 (3B)
Parity: None (3C)
Stop Bits: 1 (3D)
These settings can be changed using the navigation buttons located on the main circuit board. Refer to
the flow chart on page 14. Under the diagnostics menu, sections 3A, 3B and 3C all deal with adjusting
the Modbus settings.5.1 Boot Up and Discovery Mode
4.1 Modbus Register
To change unit ID, go into your menu under Diag, option 3A. To change your baud rate, go to Diag,
option 3B. To change parity, go to Diag, option 3C.
See below for more details
See below for more details
Flow Units (Register 40004)
• 0 = m/s
• 1 = kcfm
• 2 = cfm
• 3 = m*3/s
• 4 = fpm
• 5 = usec
Airflow Reading (40003), and 4-20mA output (40007)
The range for these registers is from -32768 to 32767. Anything greater than these values will default to
the maximum.
Error code (Register 40008)
• 0 = good reading
• 10 = obstruction. Check sensors
• 20 = above full scale