AGLAS Master Control Device
Troubleshooting and Fault Correction
© ADB SAFEGATE All Rights Reserved
18
96A0480 Rev. B
2.6 Troubleshooting and Fault Correction
Based on the fault pattern (see table), identify and remove the unit in question from the AGLAS Master, check and in case of
malfunction, replace it with a new one in accordance with the information in Table 1.
The fault correction is described in so far as it applies to the AGLAS Master.
Table 1: AGLAS Master: Fault patterns, fault location and fault correction
Fault pattern Fault location Fault correction
Long reaction times or no
reaction of the Remotes to
power-line communication in the
series circuit
Constant current regulator shuts
down the series circuit.
Cause may be a short circuit in
the series circuit.
Constant current regulator shuts
down the series circuit.
Cause may be a break in the
series circuit.