2.8 Technical Specifications
Table 2: AGLAS Specifications
Description Remote Master
Operating temperature -40 °C to +65 °C 0 °C to +55 °C
Storage temperature -55 °C to +85 °C -40 °C to +75 °C
Operating humidity Max. 100 % Max. 95 % non condensing
Series circuit operating voltage Max. 5000 V AC RMS
Min. / max. Power line current 1.8 up to 6.9 A RMS 1.8 up to 6.9 A RMS
Series circuit peak voltage Max. 15 kV
Maximum switching power secondary side
of transformer
300 W (single Remote)
Ch A + Ch B < 300 W (dual)
-
Maximum circuit load (CCR power) 30 kVA
Power consumption Max. 8 W at 6.6 A
Max. 15 W for power supply 115-230 V
Max. 65 W on primary circuit at 6.6 A
Enclosure protection level IP 68 / NEMA 6 P IP 20
LAN connection to upper control system IEEE 802.3 100 BaseT / IEEE1588 PTP
Net voltage of power supply 115 - 230 V AC ±15 %, 50/60 Hz
MTBF > 200.000 h > 200.000 h
Indicative MTTR < 30 min < 60 min
Lightning protection 20 kA (8/20 micro sec.) 17 kA (8/20 micro sec.)
EMC (CE approved)
Compliant to the EN 61000-6-4 (EMC emission standard) Compliant to the EN 61000-
6-2 and 6-5 (EMC immunity standard) Compliant to the 60950 (IT equipment
standard)
Power Up Mode On; Off; Flashing; Maintained (last commanded state)
Fail-Safe Mode On; Off; Flashing, Maintained (last commanded state)
Number of controlled and monitored
lamps per unit
1 or 2
Up to 300 Remotes or 600 lights, if dual
Remotes are used
Number of I/O Remotes per circuit Max. 16
Transmit Frequency 11 different frequency bands between 20 kHz and 200 kHz
Data transmission rate power line Up to 8 kbps Up to 8 kbps
Dimensions (W x H x D) / Weight
208 x 78 x 142 / 2,2 kg (single Remote)
/2,3 kg (dual)
435,8 x 177,5 x 421,5mm / 22,3 kg
Lamp failure reaction
Short is placed across isolation
transformer as soon as lamp filament
failure detected
Power Storage after Power-Off
Remote does not reset and remains in
operation, if circuit power loss < 1.5 sec.
Remote start up time is less than 1 sec.