WFR113539-13 www.adclaundry.com 19
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For
others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
OVEN
kW
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
AD-35i
Single-Phase Heat, Single-Phase Motor
208 2 13.5 71.7 90
220 2 11.3 58.0 80
220 2 11.3 58.0 70
230 2 12.4 60.5 60.5 80
240 2 13.5 62.9 62.9 80
Three-Phase Heat, Single-Phase Motor
220 3ø 3 11.3 34.3 34.3 50
230 3ø 3 12.4 35.7 35.7 50
240 3 13.5 37.1 37.1 50
380 3* 11.3 23.3 30
400 3* 12.4 24.0 30
416 3* 13.5 24.8 40
Three-Phase Heat, Three-Phase Motor
208 3 13.5 43 60
220 3 11.3 35 35 50
230 3 12.4 37 36 50
240 3 13.5 38 38 50
380 3 11.3 21 30
400 3ø 3 12.4 21 30
416 3ø 3 13.5 22 30
440 3ø 3 11.3 19 30
460 3ø 3 12.4 20 30
480 3ø 3 13.5 20 30
AD-50i / M-50p
Single-Phase Heat, Single-Phase Motor
208 2 22 115.9 150
220 2 18.5 94.0 89.0 125
230 2 20.4 98.6 93.6 125
240 2 22 101.7 150
240 2 22 96.6 125
Three-Phase Heat, Single-Phase Motor
208 3 22 67.8 90+
220 3 18.5 55.0 53.4 70
230 3 20.4 57.7 56.1 80
240 3 22 59.5 57.8 80
380 3* 18.5 34.7 50
400 3* 20.4 36.1 50
416 3* 22 37.2 50
Three-Phase Heat, Three-Phase Motor
208 3 22 70 90
220 3 18.5 57 80
220 3 18.5 55 70
230 3 20.4 60 58 80
240 3 22 61 59 80
380 3 18.5 33 33 50
400 3 20.4 34 50
416 3 22 35 50
440 3 18.5 29 40
460 3 20.4 30 40
480 3 22 31 40
Electric Models Only (AD-35i, AD-50i/M-50p)
Check your national and local codes for breaker and wire sizes. 5/9/18
* If configuration ordered is one phase motor, three phase heat dryer will be
4-wire.
Check your national and local codes for breaker and wire sizes. 5/9/18
* If configuration ordered is one phase motor, three phase heat dryer will be
4-wire.
Grounding
A ground (earth) connection must be provided and installed
in accordance with local, state, and national regulations or
codes of the country of origin. In the absence of these codes,
grounding must conform to applicable requirements of the
National Electrical Code ANSI/NFPA NO. 70-LATEST
EDITION, or in Canada, the installation must conform to
applicable Canada Standards: Canadian Electrical Codes
Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION. The ground
connection may be to a proven earth ground at the location
service panel.
For added personal safety, when possible, it is suggested that
a separate ground wire (size per local codes) be connected
from the ground connection of the dryer to a grounded cold
water pipe. Do not ground to a gas pipe or hot water pipe.
The grounded cold water pipe must have metal-to-metal
connection all the way to the electrical ground. If there are
any nonmetallic interruptions, such as, a meter, pump, plastic,
rubber, or other insulating connectors, they must be jumped
out with a wire (size per local codes) and securely clamped to
bare metal at both ends.
Electric Models Only (AD-80i/M-80p)
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For
others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
OVEN
kW
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
AD-80i / M-80p
Single-Phase Heat, Single-Phase Motor
208 2 22 116.1 150
220 2 18.5 94.0 89.0 125
230 2 20.4 98.6 93.6 125
240 2 22 101.7 150
240 2 22 96.6 125
Three-Phase Heat, Single-Phase Motor
208 3 22 71.4 90
220 3 18.5 58.5 53.4 70
230 3 20.4 61.2 56.1 80
240 3 22 63.0 57.8 80
380 3* 18.5 34.7 50
400 3* 20.4 36.1 50
416 3* 22 37.2 50
Three-Phase Heat, Three-Phase Motor
208 3 22 69 90
220 3 18.5 57 80
220 3 18.5 55 70
230 3 20.4 60 58 80
240 3 22 61 59 80
380 3 18.5 33 50
400 3 20.4 34 50
416 3 22 35 50
440 3 18.5 29 40
460 3 20.4 30 40
480 3 22 31 40