18 American Dryer Corp. WFR113539-13
Electrical Information _________________
Electrical Requirements
All electrical connections must be made by a properly licensed
and competent electrician. This is to ensure that the electrical
installation is adequate and conforms to local, state, and
national regulations or codes of the country of origin. In the
absence of such codes, all electrical connections, materials,
and workmanship must conform to the applicable requirements
of the National Electrical Code ANSI/NFPA NO. 70-LATEST
EDITION or in Canada, the Canadian Electrical Codes Parts
1 & 2 CSA C22.1-1990 or LATEST EDITION.
IMPORTANT: Failure to comply with these codes or
ordinances, and/or the requirements stipulated in this
manual can result in personal injury or component failure.
NOTE: Component failure due to improper installation will
void the warranty.
Each dryer should be connected to an independently protected
branch circuit. The dryer must be connected with copper wire
only. Do not use aluminum wire, which could cause a fire
hazard. The copper conductor wire/cable must be of proper
ampacity and insulation in accordance with electric codes for
making all service connections.
NOTE: The use of aluminum wire will void the warranty.
An individual ground circuit must be provided to each dryer,
do not daisy chain.
Component failure due to improper voltage application will
void the warranty.
The manufacturer reserves the right to make changes in
specifications at any time without notice or obligation.
IMPORTANT: A separate protected circuit must be provided
to each dryer.
The dryer must be connected to the electric supply shown
on the rating plate. In the case of 208 VAC or 240 VAC, the
supply voltage must match the electric service
specifications of the rating plate exactly.
The wire size must be properly sized to handle the related
current.
!
WARNING
208 VAC and 240 VAC are not the same. Any damage
done to dryer components due to improper voltage
connections will automatically void the warranty.
Check your national and local codes for breaker and wire sizes. 1/13/17
Electrical Service Specifications
Gas and Steam Models Only
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
AD-35i
120 2 10.2 15
200 2 7 15
208 2 6.8 15
220 2 6.6 6.6 15
230 2 6.6 6.6 15
240 2 6.6 6.6 15
208 3 5 15
220 3 5.4 3 15
230 3 5.4 3 15
240 3 5.4 3 15
440 3 3.1 15
460 3 3.1 15
480 3 3.1 15
380 3 2.5 15
400 3 2.5 15
416 3 2.5 15
AD-50i / M-50p
120 2 9.8 15
200 2 10.45 15
208 2 8 15
220 2 5 5 15
230 2 5 5 15
240 2 5 5 15
208 3 4.45 15
220 3 8.35 4.45 15
230 3 8.35 4.45 15
240 3 8.35 4.45 15
440 3 4.53 15
460 3 4.53 15
480 3 4.53 15
380 3 2.73 15
400 3 2.73 15
416 3 2.73 15
AD-80i / M-80p
120 2 9.8 15
200 2 8 15
208 2 5 15
220 2 5 5 15
230 2 5 5 15
240 2 5 5 15
208 3 8.35 15
220 3 8.35 4.45 15
230 3 8.35 4.45 15
240 3 8.35 4.45 15
440 3 4.53 15
460 3 4.53 15
480 3 4.53 15
380 3 2.73 15
400 3 2.73 15
416 3 2.73 15