Power on start lock
(External terminal
only)
CD80
Setting Range 0 ~ 3
Default Value 0
MT output signal
selection
CD81
Setting Range 0 or 1
Default Value 0
0 : Analog frequency meter. (Mix output is CD14’s setting value)
1 : Analog current meter. (When CD82=100, MT mix. Output(10V) is
250% of rated AC motor drive current)
Note : 1V represent how mach current depend model.
Example : When CD82=100 & AP2G3-337 output 17A (rated AC motor
drive current), MT output 4V.
72
CD80
Start lock
(Run when power on)
Operation status when operation
command source is changed
0
CD12=1, operation switch="ON"
AC motor drive will run
CD12=1 CD12=0, OPE7
1
CD12=1, operation switch="ON"
AC motor drive doesn't run
CD12=1 CD12=0
Keep previous status
2
CD12=0, operation switch="ON"
AC motor drive will run
CD12=0 CD12=1, AC motor
drive will run
3
CD12=0, operation switch="ON"
AC motor drive doesn't run
CD12=0 CD12=1, AC motor
drive doesn't run. operation switch
need "OFF" then "ON". AC motor
drive will run.
→
→
→
→