41
Fourth speed
setting
CD24
Terminal
order
SPEED
CF1 CF2
SPEED - 1 OFF OFF
SPEED - 2 ON OFF
SPEED - 3 OFF ON
SPEED - 4 ON ON
Acceleration time 2
CD25
Setting Range 0.0 ~ 1200HZ
Default value 40.0HZ
ON
ON ON
ON
Operation Signal
Output frequency
Terminal CF1
Terminal CF2
Speed 1
Speed 2
Speed 3
Speed 4
Speed 1
CD42 or CD43 setting FT1 or FT2=3, then CD25 or CD26 can be used.
Deceleration time 2
CD26
Acceleration
time 2
Acceleration
time 1
Time(Sec)
Deceleration time 1
Deceleration time 2
2CH=OFF
2CH=ON
2CH=ON
2CH=OFF
F
(HZ)
Description 2CH
Acceleration time 1
OFF
Deceleration time 1
Acceleration time 2
ON
Deceleration time 2
To operate inverter with 2CH function, check to see CD42 or CD43=3.
2CH command inputs from FT1 or FT2 terminal.
Setting Range 0.1 ~ 6000.0Sec
Default value 10.0Sec
Setting Range 0.1 ~ 6000.0Sec
Default value 10.0Sec