4-48 ADAM 4000 Series User's Manual
$AA2
Name Configuration Status
Description The command requests the return of the configuration data
from the analog input module at address AA.
Syntax $AA2(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module that you want to
interrogate.
2 is the Configuration Status command.
(cr) is the terminating character, carriage return (0Dh).
Response !AATTCCFF(cr) if the command is valid.
?AA(cr)if an invalid
operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
!
delimiter character indicates a valid command was received.
?
delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
TT represents the type code. Type code determines the input
range.
CC represents the baud rate code.
FF is a hexadecimal number that equals the 8-bit parameter that
represents the data format, checksum status and integration
time . The layout of the 8-bit parameter is shown in figure 4-1.
Bits 2 to 5 are not used, and are set to 0.
(cr) is the terminating character, carriage return (0Dh).
(Also see the %AANNTTCCFF configuration command)
4011, 4011D, 4012, 4013, 4015, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019