Chapter 4 Command Set 4-57
$AA0
Name Span Calibration
Description Calibrates an analog input module to correct for gain errors.
Syntax $AA0(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module which is to be calibrated.
0 represents the span calibration command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
!
delimiter character indicates a valid command was received.
?
delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
(cr) represents terminating character, carriage return (0Dh).
In order to successfully calibrate an analog input module’s input range, a
proper calibration input signal should be connected to the analog input
module before and during the calibration. (See also Chapter 5, Calibration)
NOTICE: An analog input module requires a maximum of 7 seconds to
perform auto calibration and ranging after it received a Span Calibration
command . During this interval, the module can not be addressed to
perform any other actions.
4011, 4011D, 4012, 4013, 4016,
4017, 4017+, 4018, 4018+, 4018M