4-98 ADAM 4000 Series User's Manual
Command Set
4018M
@AARNNNN
HHHH represents the 4-character hexadecimal number of
returned record stored in the analog input data logger at
address AA.
TTTTTTTT represents elapsed time.
(cr) is the terminating character, carriage return (0Dh).
Example command: @F3R1000(cr)
response: !F30799AA00001000(cr)
The command requests the analog input data logger at address
F3 to return its contents in the 1001st record.
The returned content is valid. The event data number is
- 39.338 for channel 0 in the 4096 seconds from the start of the
module.