4-146 ADAM 4000 Series User's Manual
Command Set
4021
About System / CH Setting
Command Set Function Response Example Note T0
$AA8Cn Read Back CHn Output Range !AACnxx $027C2 !02C232 1ms
$AAACnZ Enable/Disable (Z=1/0) CHn EMS Flag !AA $02AC21
$02AC20
!02 1ms
$AABCn Read CHn EMS Flag !AACn1
!AACn0
$02BC2 !02C21
!02C20
1ms
$AADCn Read Back CHn StartUp Data !AA(data) $02DC2 !02+07.456 4ms
$AAECn Read Back CHn Emergency Stop Data !AA(data) $02EC2 !02+07.456 4ms
$AAF Read Firmware Version !AAAx.xx $02F !02A0.00 300us
$AAG Reset Current Trim Data Variable To 0 !AA $02G !02 300us
$AAH Read Current Trim Data Variable !AAxx
(xx=m)
$02H !0208 300us
$AAI Read IDI !AAx $02I !02F 300us
$AAM Read Module Name !AA4024 $02M !024024 300us
$AANCn Read Back CHn 4mA Calibration Parameter !AAxx $02NC2 !0206 900us
$AAOCn Read Back CHn 20mA Calibration Parameter !AAxx $02OC2 !020D 900us
$AAPCn Clear CHn 4mA Calibration Parameter /
EEPROM
!AA $02PC2 !02 300us
$AAQCn Clear CHn 20mA Calibration Parameter /
EEPROM
!AA $02QC2 !02 300us
Isolation Digital Input Definition :
Active : No Matter Active High Or Low The Firmware Must Read Set Status
( On , 1 )
Command : $AA5
This Command Return The Module Reset Times From Last
$AA5 Executed, And Then The Reset Times Memory Clear To 0
EX. The Following Procedure Never Reset Module
$025 !0203
$025 !0200
$025 !0200
EX. The Following Procedure
$025 !0203
$025 !0200
Now Reset Module
$025 !0201