4-172 ADAM 4000 Series User's Manual
Command Set
4080, 4080D
$AAM
Name Read Module Name
Description The command requests the counter/frequency module at
address AA to return its name
Syntax $AAM (cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency module that you want to
interrogate.
M identifies the Read Module Name command.
(cr) is the terminating character, carriage return (0Dh)
Response !AA(Module Name)(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error, or if the specified address does not exist.
! is a delimiter character indicating a valid command was
received.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency module.
(Module Name) is the name of the module at address AA. For
example: 4080D
(cr) is the terminating character, carriage return (0Dh).