4-174 ADAM 4000 Series User's Manual
Command Set
4080, 4080D
$AAB
Name Read Input Mode.
Description Read the input mode of the specified counter/frequency
module.
Syntax $AAB(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency that you want to interrogate.
B identifies the Read Input Signal Mode command.
(cr) is the terminating character, carriage return (0Dh)
Response !AAS(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error, or if the specified address does not exist.
! delimiter character indicating the command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter/frequency module.
S indicates the input signal mode. S = 0 configures the module
for non-isolated (TTL) input and S = 1 configures the module
for photo-isolated input.
(cr) is the terminating character, carriage return (0Dh).
Example command: $03B(cr)
response: !030(cr)
The command requests the counter/frequency module at
address 03 to return its input mode. The addressed module
replies that its input mode is set to receive non-isolated input.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals