EasyManuals Logo

Advantech Adam 4000 Series User Manual

Advantech Adam 4000 Series
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #270 background imageLoading...
Page #270 background image
4-186 ADAM 4000 Series User's Manual
4080, 4080D
Command Set
$AA6N
Name Clear Counter
Description Clears the counter 0 or counter 1 of the specified counter/
frequency module.
Syntax $AA6N(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency module that you want to interro-
gate.
6 the Clear Counter command.
N determines the counter which should be cleared.
N = 0 represents counter 0
N = 1 represents counter 1
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! is a delimiter character indicating the command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter input module.
(cr) is the terminating character, carriage return (0Dh).
Example command: $1361(cr)
response: !13(cr)
The command requests the counter/frequency module at
address 13 to clear counter 1. The addressed module replies
with its address to indicate the counter has been cleared.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals