Chapter 4 Command Set 4-185
4080, 4080D
Chapter 4
$AA5N
Name Read Counter Start/Stop Status
Description Requests the addressed counter/frequency module to indicate
whether counter 0 or counter 1 is active.
Syntax $AA5N(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency module that you want to interro-
gate.
N determines the counter for which the status should be
returned.
N = 0 represents counter 0
N = 1 represents counter 1
(cr) is the terminating character, carriage return (0Dh)
Response !AAS(cr) if the command is valid.
There is no response if the module detects a syntax or commu-
nication error, or if the specified address does not exist.
! is a delimiter character indicating the command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter input module.
S represents the counter status.
S = 0 indicates counting
S = 1 indicates not counting
(cr) is the terminating character, carriage return (0Dh).
Example command: $0650(cr)
response: !061(cr)
The command requests the counter/frequency module at
address 06 to return the status of counter 0. The addressed
module replies that counter 0 is counting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals