EasyManuals Logo

Advantech Adam 4000 Series User Manual

Advantech Adam 4000 Series
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #274 background imageLoading...
Page #274 background image
4-190 ADAM 4000 Series User's Manual
Command Set
4080, 4080D
$AA4S
Name Enable/Disable Digital Filter
Description Enables or disables the digital filter of the addressed counter/
frequency module
Syntax $AA4S(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency module that you want to interro-
gate.
4 identifies the Enable/Disable Filter command
S is the digital filter mode.
S = 0 means disable filter
S = 1 means enable filter
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid.
There is no response if the module detects a syntax or commu-
nication error, or if the specified address does not exist.
! is a delimiter character indicating the command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter input module.
(cr) is the terminating character, carriage return (0Dh).
Example command: $0340(cr)
response: !03(cr)
The command orders the counter/frequency module at address
03 to disable its digital filter. The addressed module returns its
address to indicate that it has executed the command success-
fully.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals