4-204 ADAM 4000 Series User's Manual
4080
Command Set
@AAGN
Name Read Initial Count Value of Counter 0 (or 1)
Description Read the initial count value of counter 0 or 1 of the specified
counter module at address AA.
Syntax @AAGN(data)(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
GN represents the Read Initial Count Value for counter com-
mand.
N = 0 represents counter 0
N = 1 represents counter 1
(cr) is the terminating character, carriage return (0Dh).
Response !AA(data)(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! is a delimiter character indicating a command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
(data) is the initial count value which must consist of eight
hexadecimal digits.
(cr) is the terminating character, carriage return (0Dh).
Example command: @12G0(cr)
response: !12000000FF(cr)
The command instructs the module at address 12h to return the
initial value of counter 0. The module replies that initial count
value of counter 0 is 000000FF.