I/O Modules
3-24 ADAM 4000 Series User's Manual
Jumper setting
1. JP9 and JP10 (default setting is six differential and two single-ended)
2. JP1~JP8
3. JP13
Technical specification of ADAM-4017+
Eight differential
JP9, Jp10
Six differential and two single-ended
Voltage Input range
JP1~JP8
20mA Input Range
Mapping to Channel
Ch.1 Ch.2 Ch.3 Ch.4 Ch.5
Ch.6
Ch.7
Ch.8
JP 1 JP 3 JP 5 JP 7 JP 2 JP 4 JP 6
System is initial mode
Jp13
System is normal mode
Channel
8
Input Type
mV,V,mA
Input range
+/-150mV,+/-500mV,+/-1V,+/-5V,+/-10
V, + /- 2 0 m V, 4 ~ 2 0 m A
Isolation Voltage
3000 V
DC
Fault and overvoltage
protection
With stands overvoltage up to +/-35 V
Sampling Rate
10 sample/sec (total)
Input Impedance
20 M
Accuracy +/- 0.1% or better
Power Consumption 1.2 W