Chapter 4 Command Set 4-11
Chapter 4
ADAM-4015 Command Table
Command Syntax Command Name Command Description Page No.
%AANNTTCCFF Configuration Sets the address, baud rate, data format,
checksum status, and/or integration time
for a specified analog input module
4-44
#AAN Read Analog Input from
Channel N
Returns the input value from a specified
channel of analog input module in the
currently configured data format
4-54
#AA Analog Data In Returns the input value from a specified
analog input module in the currently
configured data format
4-52
$AA0Ci Single Channel Span
Calibration
Calibrates a specified channel to correct for
gain errors
4-65
$AA1Ci Single Channel Offset
Calibration
Calibrates a specified channel to correct for
offset errors
4-66
$AA2 Configuration Status Returns the configuration parameters for
the specified analog input module
4-58
#** Synchronized Sampling Orders all analog input modules to sample
their input values and store them in special
registers
4-59
$AA4 Read Synchronized Data Returns the value that was stored in the
specified module’s register after the #**
command
4-60
$AA5VV Enable/Disable Channels
for Multiplexing
Enable or disable the individual channels in
an analog module
4-55
$AA6 Read Channel Status Get the enable/disable status of all channels
in an analog module
4-56
$AAB Channel Diagnose Diagnose channel status in over range,
under range, and wire opening
4-62
$AA7CiRrr Single Channel Range
Configuration
Configure the input type and range of the
specified channel in an analog input module
4-67
$AA8Ci Read Single Channel
Range Configuration
Get the input type and range of the
specified channel in an analog input module
4-70
$AAXnnnn Watchdog Timer Setting Set WDT communication cycle 4-71
$AAY Read Watchdog Timer
Setting
Read the setting of WDT communication
cycle
4-72
$AAS0 Internal Calibration Internal self-calibration for offset and gain
errors
4-73
$AAS1 Reload default calibrating
parameter
Reload factory default calibrating parameter
to overwrite current calibrating parameter
4-74
$AAF Read Firmware Version Return the firmware version code from the
specified analog input module
4-50
$AAM Read Module Name Return the module name from the specified
analog input module
4-51