103 WISE-4000 User Manual
Appendix A I/O Modbus Mapping Table
40301 All DI DI Value Read
40303 All DO DO Value R/W
40001 0
AI Value
(Value Range: 0~10000,
Value Unit: mV)
Read
40002 1 Read
40003
Average
Channel 0~1
Read
40017~40018 0
Counter/Frequency
Value
R/W
40019~40020 1 R/W
40021~40022 0
Pulse Output
Low Level Width
R/W
40023~40024 1 R/W
40025~40026 0
Pulse Output
High Level Width
R/W
40027~40028 1 R/W
40029~40030 0 Set Absolute
Pulse Output Number
(0 for continuous output)
R/W
40031~40032 1 R/W
40033~40034 0
Set Incremental
Pulse Output Number
R/W
40035~40036 1 R/W
40101~40102 0
AI Status*
Read
40103~40104 1 Read
40111 0
Historical
Maximum AI Value
Read
40112 1 Read
40113
Average
Channel 0~1
Read
40121 0
Historical
Minimum AI Value
Read
40122 1 Read
40123
Average
Channel 0~1
Read
40131~40132 0
AI Floating Value
(IEEE754)
Read
40133~40134 1 Read
40135~40136
Average
Channel 0~1
Read
40151~40152 0
Historical Maximum
AI Floating Value
(IEEE754)
Read
40153~40154 1 Read
40155~40156
Average
Channel 0~1
Read