29 WISE-4000 User Manual
Chapter 2 Product Specifications
2.7.4 Block Diagram
Figure 2.26 WISE-4050 Block Diagram
2.8 WISE-4051
2.8.1 I/O Specification
Digital Input
Channel: 8
Logic level
Dry Contact 0: Open
1: Close to DI COM
Wet Contact 0: 0~3 V
DC
or -3~0 V
DC
1: 10~30 V
DC
or -30~-10 V
DC
(3 mA min.)
Channel 0~3 should be configured to dry contact or wet contact in the same
time
Channel 4~7 should be configured to dry contact or wet contact in the same
time
Isolation: 3,000 V
rms
Supports 32-bit Counter Input Function (Maximum signal frequency 3 kHz)
Keep/Discard Counter Value when Power-off
Supports Frequency Input Function (Maximum frequency 3 kHz)
Supports Inverted DI Status
RS-485 Port
Number of Ports: 1
Port Connector: 3.5mm spacing plug-in screw terminal block (shared with I/O
and power)
Baud Rate (bps): 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Data Bits:7, 8
Stop Bits: 1, 2
Parity: None, Odd, Even
Flow Control: Auto flow control
Signals: DATA+ and DATA-
Protection: 15 kV ESD
Supported Protocol:
Modbus/RTU (Total 32 address by max. 8 instructions)

Table of Contents