65 WISE-4000 User Manual
Chapter 4 System Configuration
In previous figure we demonstrate how to configure an ADAM-4017+ (or ADAM-
4117) which slave ID is 1 and an ADAM-4055 which slave ID is 2 as the Modbus
slave devices connected to WISE-4051.
ADAM-4017+ (or ADAM-4117) is an 8-ch analog input Modbus I/O modules, the
Modbus address of AI0~AI7 are 40001~40008. In the Rule Setting page, we config-
ure the Slave ID = 1; Type = 03 Holding Registers, since the Modbus address 40001
is start from 4; Start Address = 1 and Length = 8 for the address 40001~40008; R/
W = R, since this address is for analog input which is read only; Scan Interval =
1000ms for polling every second; Mapping Channel = 0, to mapping the data from
AI0~7 of ADAM-4017+ to channel 0~7 of Word Status; and check the Log to log the
data from ADAM-4017+.
ADAM-4055 is an 8-ch digital input and 8-ch digital output Modbus I/O modules, the
Modbus address of DI0~DI7 are 00001~00008; the Modbus address of DO0~DO7
are 00017~00024. Since the address is not continuously, so we are going to config-
ure digital input as one rule, and digital output as another rule.
For digital input channels: In the Rule Setting page, we configure the Slave ID = 2;
Type = 01 Coil Status, since the Modbus address 00001 is start from 0; Start
Address = 1 and Length = 8 for the address 00001~00008; R/W = R, since this
address is for digital input which is read only; Scan Interval = 1000ms for polling
every second; Mapping Channel = 0, to mapping the data from DI0~7 of ADAM-
4055 to channel 0~7 of Bit Status; and check the Log to log the data from ADAM-
4055. Please be noted that the Bit Status and Word Status have individual channel
number, so the Word Status for ADAM-4017+ and the Bit Status for ADAM-4055 are
all start from 0.
For digital output channels: In the Rule Setting page, we configure the Slave ID = 2;
Type = 01 Coil Status, since the Modbus address 00017 is start from 0; Start
Address = 17 and Length = 8 for the address 00017~00024; R/W = R/W, since this
address is for digital output which can be wrote and read, you can also configured as
W if you don't want to read back the value; Scan Interval = 1000ms for polling every
second; Mapping Channel = 8, to mapping the data from DO0~7 of ADAM-4055 to
channel 8~15 of Bit Status; and check the Log to log the data from ADAM-4055.
Please be noted that the channel 0~7 of Bit Status have been occupied by previous
rule, so you should assign the channel number from channel 8~31.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech WISE-4000 Series and is the answer not in the manual?

Advantech WISE-4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelWISE-4000 Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals