EasyManua.ls Logo

AEG ME09 - OPERATION; OPERATING MODES; SETUP MODE; Entering Set points into Memory

AEG ME09
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mpro Trip Units have four operaƟng modes: Setup, Meter,
Status and Events. These are accessed through the Įve keys on
the Trip Unit front.
SETUP Mode programming must be performed with the raƟng
plug installed. This procedure apply to all trip unit types.
The SETUP procedures should only be repeated if the trip unit or
the protecƟon characterisƟcs are changed, requiring diīerent
set points and Ɵmedelays.
All trip units provide long Ɵme over current protecƟon, long
Ɵme delay, and some form of short circuit current protecƟon
when installed in circuit breakers. All other funcƟons are
opƟonal.
If a speciĮc set of trip unit funcƟons, such as relaying or short
Ɵme over-current protecƟon is not installed that funcƟon will
not appear on the trip unit display. Ignore setup mode
instrucƟons
for such funcƟons.
The trip unit must be powered by one of the indicated four
methods during SETUP. (see par. 2.1.9)
-- Press UP or DOWN unƟl the SETUP mode is selected.
-- Press RIGHT or LEFT to access the funcƟons in the SETUP
mode.
-- Press ENTER to save desired values.
-- Press RIGHT to advance to the next funcƟon.
1. Press UP or DOWN to select SETUP.
2. Press LEFT or RIGHT to select the desired protecƟon to
change.
3. Press UP or DOWN to change values. The values will start
Ňashing.
4. Press ENTER to store the value into the memory. The
displayed value stops Ňashing and the save icon appears on the
top of the LCD. This indicates that the value has been stored in
memory and is acƟve.
5. ConĮrm seƫngs on the trip unit aŌer making changes by
exiƟng and re-entering SETUP mode and rechecking each
changed seƫng.
2.2 ֡ፕ
2.2.1!֡ፕఇ๕
2.2.2 SETUPDŽยዃDžఇ๕
Nqspۉጱྃഗᆶ! 5! ዖ֡ፕఇ๕ǖยዃĂᅏ՗Ăጒༀ
ࢅ๚ăᅜ๑ᆩۉጱྃഗኟ௬ฉڦ! 6! ߲Ӏ৊ႜ
֡ፕă
..!VQDŽၠฉDžǖၠฉࡐۯሺຕኵă
..!EPXODŽၠူDžǖၠူࡐۯၭຕኵă
..!SJHIUDŽၠᆸDžǖူᅃࠀీူᅃᄻă
..!MFGUDŽၠፑDžǖฉᅃࠀీฉᅃᄻă
..!FOUFSDŽඓۨDžǖԍ٪ยዃڟ٪ئഗዐă
TFUVQDŽยዃDžఇ๕ՊײՂႷሞҾጎᆶܮ֭ۨཀྵڦཉူ
৊ႜă޿ײႾ๢ᆩᇀ໯ᆶ႙ࡽڦۉጱྃഗă
TFUVQDŽยዃDžײႾৈሞۉጱྃഗԍࢺ༬ኙ߀ՎLj
Ⴔᄲփཞڦยዃۅࢅ้ჽ׿้ዘްሏႜă
Ҿጎሞ܏ୟഗዐ้Lj໯ᆶۉጱྃഗۼᆶ׊้ࡗۉୁ
ԍࢺĂ׊้ჽ้ࢅևݴႚ๕ڦ܌ୟۉୁԍࢺࠀీăഄ໱
໯ᆶࠀీྺ჋ၜă
සࡕுᆶҾጎ༬ۨڦۉጱྃഗࠀీDŽසۉഗ܌้ࡗ
ۉୁԍࢺDžLjሶ޿ࠀీփࣷ၄ሞۉጱྃഗ၂๖ೡฉă
൩ࢮ୼ኄၵࠀీڦยዃఇ๕ຫ௽ă
TFUVQDŽยዃDž೺LjՂႷཚࡗᅜူ! 5! ዖݛ݆ኮᅃഔۯ
ۉጱྃഗăDŽ֖!3/2/:!বDž
..! Ӏူ! VQDŽၠฉDž! EPXODŽၠူDžLj኱ڟ჋ዐ!
TFUVQDŽยዃDžఇ๕ă
..! Ӏူ! SJHIUDŽၠᆸDž!MFGUDŽၠፑDžሞTFUVQ
DŽยዃDžఇ๕ዐ჋ስࠀీă
..!Ӏူ!FOUFSDŽඓණDžԍ٪໯Ⴔڦኵă
..!Ӏူ!SJHIUDŽၠᆸDžገڟူᅃࠀీă
2/! Ӏူ! VQDŽၠฉDž! EPXODŽၠူDž჋ስTFUVQ
DŽยዃDžă
3/! Ӏူ! MFGUDŽၠፑDž! SJHIUDŽၠᆸDž჋ስၙᄲ߸
߀ڦԍࢺă
4/!Ӏူ!VQDŽၠฉDž!EPXODŽၠူDž߸߀ຕኵăຕኵ
๔෻ۯă
5/! Ӏူ! FOUFSDŽඓණDžຕኵ٪ئڟ٪ئഗዐă໯၂
๖ڦኵཕኹ෻ۯLjԍ٪཮Ք၄ሞ!MDE!ฉ܋ăኄ՗๖޿ຕ
ኵᅙ٪ئڟ٪ئഗዐ൐ᅙഔᆩă
6/! ৊ႜ߸߀ࢫLjཽժዘႎ৊෇! TFUVQDŽยዃDžఇ๕Lj
ްࢃ߲߳߸߀ڦยዃLjܸٗඓණۉጱྃഗฉڦยዃă
2.2.2.1!ยዃۅ๼෇٪ئ
TRIP UNIT
ཌቄڇᇮ
֡ፕ
2.2
2.2-01
2.2 OPERATION
2.2.1 OPERATING MODES
2.2.2 SETUP MODE
2.2.2.1 Entering Set points into Memory
-- UP: Scroll up or increment value
-- DOWN: Scroll down or decrement value
-- RIGHT: Next funcƟon or next page
-- LEFT: Previous funcƟon or previous page
-- ENTER: Save or set in to memory
཮!3/6!
ၠฉ
ၠူ
ၠᆸDŽူᅃ߲Dž
ၠፑDŽฉᅃ߲Dž
ඓණDŽԍ٪Dž
Fig 2.2 Key pad
Up
Down
Right (Next)
LeŌ (Previous)
Enter (Save)
NF1:ဣଚگუഘ܏ୟഗ

Related product manuals